Manufacturing Method and Installation Precautions for Copper Bars of Switchgear


Release time:

2024-05-23

Switch cabinet copper bar is the key equipment in the power transmission system

Switch cabinet copper bar is the key equipment in the power transmission system, so it must be strict in both production and installation to avoid potential safety hazards. Today, the editor will talk about the production method and installation precautions of switch cabinet copper bar. Let's learn about it together!

1. switch cabinet copper bar production method

1. Determine the safety distance

The safe creepage distance of different cabinet types should be understood first. The distance between phases and relative ground of low-voltage cabinets must be above 20mm. Although the relevant standard is 0.8cm, the safe electricity consumption requirement in the industry is 20mm, so it must be above 20mm. High voltage 10KV safety distance is more than 125mm, high voltage 35KV safety distance is 300mm, the requirements of different companies will be different.
Copper Bow
2. Select copper bar size

The usage of general copper bars is basically the same, with rated current 125A using 15*3,200A using 20*3,400A using 30*4, 630A using 40*6 or 50*5, 800 using 40*10 or 50*8,1000A using 60*8, 1600A using 100*8, 2000A using 100*10, 2500A using 100*8 double rows, 100*10 pairs for 3000A, 120*10 pairs for 3500A and 3 rows of 120*10 for 4000A.

The copper bar on the knife switch: 600 knives 40*5, 1000 knives 60*6, 1500 knives 80*8, 2000 knives 100*10, etc. However, the standard requirements of different companies are also different, so they can be selected according to the actual situation.

3. Measurement

Measurement is a difficult step in the process of copper bar manufacturing. Its main purpose is to find the right reference or base point. Take GGD outlet cabinet as an example: when measuring the height from the contact on the knife switch to the bus bar, you can measure the height from the beam to the upper side of the bus bar at the bus bar, and then measure the height from the beam to the contact on the knife switch, add the two values to get the height of the copper bar.

The bending angle of the copper bar can be measured with the column as the base point. The distance from the column to the ABC three-phase busbar is measured first, and then the distance from the column to the contact on the knife switch is measured, and the dimensions are all out.

4. Making copper bar

After measuring the size, the copper bar can be made. It should be noted that the lap joint between the copper bars should be opened according to the standard, and the bolts should be installed according to regulations before being imprisoned. One M12 screw in 40-wide copper row, two M10 screws in 50-wide or one M16 screw, four M10 screws in 60-wide copper row, four M12 screws in 80-wide copper row, four M16 screws in 100-wide copper row and four M18 screws in 120-wide copper row. At the same time, the overlapping part of the copper bar should be embossed and electroplated, and then the heat-shrinkable tube with yellow, green, red and blue color separation can be used.

5. Install copper bar

When installing the copper bar, you should pay attention to the alignment of the lap joint, and there should be no protruding water chestnut. The screws must be tightened. Pay attention to safe operation during installation. Let's take a look at what we need to pay attention to during installation!
 

Quote Immediately

Fill out the message form and leave your contact information. Our staff will contact you within 24 hours (weekdays)
%{tishi_zhanwei}%